STATE OF WASHINGTONDEPARTMENT OF LABOR AND INDUSTRIESField Services & Public SafetyFactory Assembled StructuresPO Box 44430 Olympia, Washington 98504-4430Conversion Vendor/Medical Mobile UnitsRegulationsFood trucks, concession trailers and mobile medical units, used in Washington State are inspectedby the Department of Labor & Industries, Field Services and Public Safety Division and are to beconstructed to comply with the following codes. Copies of the Factory Built Structures WACRules are enclosed. Washington State Amendments and Washington State Building Codes areavailable from Washington Association of Building Officials.1. Rules for Conversion Vendor Units & Medical UnitsChapter 296-150V WAC (Dated 6/21/2016)(Enclosed)Note: As rules are updated they will be available on our oodTruckTrailer/default.aspWhat codes apply to conversion vendor units or medical units?(2) A conversion vendor unit or medical unit must comply with the following codes whereapplicable:(a) The International Mechanical Code (current edition), with the amendments made by theWashington State Building Code Council, chapter 51-52 WAC.(b)(i) For conversion vending units Article 551, Parts I through VI of National ElectricalCode/National Fire Protection Agency (NFPA) 70, (current edition), or Article 552, Parts Ithrough V Article of National Electrical Code/National Fire Protection Agency (NFPA) 70,(current edition),(ii) For medical units the current edition National Electrical Code as referenced in chapter19.28 RCW and chapter 296-46B WAC, installing electric wires and equipment.
(c) Chapter 7 of National Fire Protection Association (NFPA) 1192, (current edition), or theUniform Plumbing Code (current edition), as adopted and amended according to chapter 19.27RCW.(d) The Washington State Building Code Council, chapter 51-50 WAC, International BuildingCode (current edition), Chapter 11, Accessibility as applies to the exterior of the unit relating tocustomer service facilities in section 1109.11.33. Also enclosed for your use are:A.B.C.D.E.Concessionaires LetterVendor/Medical Conversion Units Pre-Inspection ChecklistSample drawing setPlan Approval request form with instructions for completingApplication for Insignia form with instructions for completingCopies of the Codes are available from:Washington Association of Building OfficialsP. O. Box 7310Olympia, WA 98507-7310Phone: 360-628-8669Web Site: wabo.orgYou should also contact your local Health Department for their requirements.
STATE OF WASHINGTONDEPARTMENT OF LABOR AND INDUSTRIESField Services & Public SafetyFactory Assembled StructuresPO Box 44430 Olympia, Washington 98504-4430MEMORANDUMMANUFACTURER ONLYTO: Food Truck and Concession Trailer Manufacturer'sFROM: Craig Sedlacek, Plan Review SupervisorSUBJECT: Manufacturer's Contact PersonnelIn order that we may serve you better we are requesting you complete the enclosed form and return it to us.By having contact persons on our mailing labels and faxes the information we are sending to you shouldbe received by those who need it. We thank you in advance for your assistance.If you have any questions, please feel free to contact me at (360)902-5218 or FAX (360)902-5229.Return to:Craig SedlacekDept. of Labor & IndustriesP O Box 44430Olympia, WA 98504-4430
MANUFACTURER ONLYFactory 1Company Name:Mailing: AddressCity: State: Zip:Physical Address:City: State: Zip:Phone No: ( ) Ext: Fax No: ( )Web Address:Contact for Plan Review:Phone No: ( ) Ext: Fax No: ( )Email Address:Contact for Plant Audit:Phone No.: ( ) Ext: Fax No: ( )Email Address:Factory # 2Company Name:(If applicable)Mailing Address:City: State: Zip:Physical Address:City: State: Zip:Phone No: ( ) Ext: Fax No: ( )Web Address:Contact for Plan Review:Phone No: ( ) Ext: Fax No: ( )Email Address:Contact for Plant Audit:Phone No.: ( ) Ext: Fax No: ( )Email Address:
Chapter 296-150V WAC:Page 1 of 36Chapter ListingChapter 296-150V WACLast Update: 12/4/18CONVERSION VENDOR UNITS AND MEDICAL UNITSWAC Sections296-150V-0010Authority, purpose, and scope.296-150V-0020What definitions apply to this chapter?296-150V-0030How is this chapter enforced?296-150V-0040Is manufacturing information kept confidential?296-150V-0050Can you prohibit the sale or lease of a conversion vendor unit or medical uni296-150V-0060Who handles consumer complaints about conversion vendor units or medica296-150V-0070Do you have reciprocal agreements with other states to inspect conversion vmedical units?296-150V-0080Do you allow a local enforcement agency to inspect conversion vendor unitsthe manufacturing location?296-150V-0100What happens if I disagree with your decision regarding my compliance with296-150V-0110Do you have an advisory board to address conversion vendor unit and medi296-150V-0120Where can I obtain technical assistance regarding conversion vendor units o296-150V-0140Do you allow the use of alternate materials, design, or method of constructio296-150V-0200Who must obtain conversion vendor unit or medical unit insignia?296-150V-0210What are the insignia requirements?296-150V-0220How do I obtain insignia information and the required forms?296-150V-0230What are the insignia application requirements?296-150V-0240What documentation do you need to perform an alteration inspection?296-150V-0250How do I replace lost or damaged insignia?296-150V-0300When is design-plan approval required?296-150V-0310Who can approve design plans?296-150V-0320What must I provide with my request for conversion vendor unit or medical uapproval by the department?296-150V-0340When is an engineering analysis or structural load test for design plans requ296-150V-0350What must test procedures and results for design plans include?296-150V-0380What happens if you approve my design plan?296-150V-0390If my design plan is not approved, how much time do I have to submit a corr296-150V-0400What happens after my design plan is approved?296-150V-0410When does my design plan expire?296-150V-0415Who approves addendums to design plans?296-150V-0495Contractor deposit cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 2 of 36296-150V-0500When is an inspection required?296-150V-0510How do I request an inspection?296-150V-0520What happens if my conversion vendor unit or medical unit passes inspectio296-150V-0530Am I charged if I request an inspection but I am not prepared?296-150V-0540Who inspects a conversion vendor unit or medical unit installation at the buillocation?296-150V-0550Do you allow a conversion vendor unit or medical unit to be completed at the296-150V-0560What happens if I receive a notice of noncompliance after inspection of the aconversion vendor unit or medical unit?296-150V-0580Must I obtain an insignia for used conversion vendor units or medical units?296-150V-0590How do I obtain insignia for used conversion vendor units or medical units?296-150V-0700Must manufacturers of conversion vendor units and medical units notify youmore than one location?296-150V-0710Must manufacturers of conversion vendor units and medical units notify youbusiness name or address?296-150V-0720Must manufacturers of conversion vendor units and medical units notify youbusiness ownership?296-150V-0800What codes apply to conversion vendor units or medical units?296-150V-0930When are structural load tests or structural calculations required?296-150V-0950What requirements apply to roof coverings?296-150V-1040Are there floor requirements?296-150V-1070What requirements apply to floor closure material?296-150V-1090What are the standards for equipment and installations?296-150V-1100What are the flame-spread limitations?296-150V-1110Combustible limitations.296-150V-1120What are the standards for wall and cabinet protection?296-150V-1170What are the light and ventilation requirements?296-150V-1180What requirements apply to conversion vendor unit exits?296-150V-1185What exit door requirements apply to self-propelled medical unit exits?296-150V-1190Interior privacy locks.296-150V-1303How must storage batteries be installed in a conversion vendor unit or medic296-150V-1330What are the mechanical requirements for a conversion vendor unit or medic296-150V-1350What are the LPG system enclosure and mounting requirements for a convemedical unit?296-150V-1360What are the fuel gas piping design requirements for a conversion vendor un296-150V-1380Can gas tubing be concealed in a conversion vendor unit or medical unit?296-150V-1390What are the pipe-joint compound requirements for gas piping in a conversiomedical unit?296-150V-1400What are the gas piping hanger and support requirements for a conversion ault.aspx?cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 3 of 36What are the electrical bonding requirements for gas piping in a conversion vunit?296-150V-1420How are gas supply connections in a conversion vendor unit or medical unit296-150V-1430What requirements apply to gas piping system openings?296-150V-1440Are gas piping shut-off valves required in a conversion vendor unit or medica296-150V-1450What requirements apply to testing for gas piping leaks before conversion veunit appliances are connected?296-150V-1460What requirements apply to testing for gas piping leaks after conversion venappliances are connected?296-150V-1470What are the requirements for appliance installations?296-150V-1530What general plumbing requirements apply?296-150V-1540What are the plumbing definitions?296-150V-1550What requirements apply to drain outlets?296-150V-1560What is the minimum clearance for drain outlets?296-150V-1570What requirements apply to water-supply connections?296-150V-1580What requirements apply to water heater relief valves and safety devices?296-150V-1590What requirements apply to waste holding tanks for conversion vendor units296-150V-1600What are the requirements associated with medical and conversion vendingmanufactured and used outside the state according to RCW 43.22.380 ?296-150V-3000Conversion vendor units and medical units—Fees.DISPOSITION OF SECTIONS FORMERLY CODIFIED IN THIS TITLE296-150V-0205 Can I obtain an exempt vendor/medical insignia? [Statutory Authority: Chapte2003 c 291. WSR 05-01-102, § 296-150V-0205, filed 12/14/04, effective 2/1/016-13-119, filed 6/21/16, effective 6/21/16. Statutory Authority: Chapter 43.22296-150V-1220 What code and installation requirements apply to conversion vendor unit or msystems? [Statutory Authority: RCW 43.22.340 , 43.22.350 , 43.22.355 , 43.243.22.432 , 43.22.433 , 43.22.434 , 43.22.450 , 43.22.480 , and 43.22.485 . W296-150V-1220, filed 8/22/00, effective 9/30/00. Statutory Authority: Chapter 418-069, § 296-150V-1220, filed 8/31/99, effective 10/1/99.] Repealed by WSR5/30/03, effective 6/30/03. Statutory Authority: RCW 43.22.340 , 43.22.400 , 443.22.434 , 43.22.480 , and 43.22.485 , 2002 c 268, and chapter 43.22 RCW296-150V-0010Authority, purpose, and scope.(1) This chapter is authorized by RCW 43.22.340 through 43.22.434 covering theconstruction, alteration, and approval of conversion vendor units and medical units sold,leased, or used in Washington state.(2) This chapter applies to the approval of conversion vendor unit and medical unitmanufacturers, dealers, and to any person who manufactures or alters the plumbing,mechanical, or electrical system of a conversion vendor unit or medical unit.https://apps.leg.wa.gov/wac/default.aspx?cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 4 of 36[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0010, filed 8/31/99,effective 10/1/99.]296-150V-0020What definitions apply to this chapter?"Alteration" is the replacement, addition, modification, or removal of any equipment orinstallation that affects the construction for concentrated floor loads, fire and life safety, or theplumbing, mechanical, and electrical systems of a conversion vendor unit or medical unit.The following are not considered alterations: Repairs with approved parts; Modifications of a fuel-burning appliance according to the listing agency'sspecifications; or Adjustment and maintenance of equipment."Approved" is approved by the department of labor and industries."Consumer" is a person or organization, excluding a manufacturer or dealer ofconversion vendor units or medical units, who buys or leases a conversion vendor unit ormedical unit."Conversion vendor unit"orunit"or "Conversion vending unit" means a motor vehicle orother structure that has been converted or built for the purpose of being used for commercialsales at temporary locations. The units must be 8 feet 6 inches or less in width (exterior floormeasurement) in the set-up position, and the inside working area must be less than 40 feet inlength (interior floor measurement). Conversion vendor units: Are transported in only one section; Are designed for highway use; Are temporarily occupied for distribution of items, e.g., food; Are built on a permanent chassis; and Include at least one of the following systems: Plumbing, mechanical or 120 and/or240 volt electrical.Note:The conversion vendor unit may NOT include a dining area."Damaged in transit" means damage that affects the integrity of a concentrated floorload design or any of the systems."Dealer" is a person, company, or corporation whose business is leasing, selling,offering for lease or sale, buying, or trading conversion vendor units, or medical units."Department" is the department of labor and industries. The department may bereferred to as "we" or "us" in this chapter. Note: You may contact us at: Department of Laborand Industries, Specialty Compliance, P.O. Box 44440, Olympia, WA 98504-4440."Design plan" is a plan for the construction or alteration of a conversion vendor unit ormedical unit or conversion of a vehicle to a conversion vendor unit or medical unit includingfloor plans, specifications, or test results necessary for a complete evaluation of the design, ifapplicable."Design option" is a design that a manufacturer may use as an option to itsconversion vendor unit or medical unit design plan."Educational facility" is a building or portion of a building used primarily foreducational purposes by six or more persons at one time for twelve hours per week or fourhttps://apps.leg.wa.gov/wac/default.aspx?cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 5 of 36hours in any one day. Educational occupancy includes: Schools (preschool through gradetwelve), colleges, academies, universities, and trade schools."Equipment" is all material, appliances, devices, fixtures, fittings, or accessories usedin the manufacture, assembly, conversion to, or alteration of a conversion vendor unit ormedical unit."Factory assembled structure (FAS) advisory board" is a board authorized toadvise the director of the department regarding the issues and adoption of rules relating toconversion vendor units and medical units."Health or personal care facilities" are buildings or parts of buildings that contain,but are not limited to, facilities that are required to be licensed by the department of social andhealth services or the department of health (e.g., hospitals, nursing homes, private alcoholismhospitals, private psychiatric hospitals, boarding homes, alcoholism treatment facilities,maternity homes, birth centers or childbirth centers, residential treatment facilities forpsychiatrically impaired children and youths, and renal hemodialysis clinics) and medical,dental or chiropractic offices or clinics, outpatient or ambulatory surgical clinics, and suchother health care occupancies where patients who may be unable to provide for their ownneeds and safety without the assistance of another person are treated. (Further defined inWAC 296-46B-010296-46B-010.).)"Insignia" is a label that we attach to a conversion vendor unit or medical unit to verifythat the structure meets the requirements of this chapter and the applicable codes."Install" is to erect, construct, assemble, or set a conversion vendor unit or medicalunit in place."Institutional facility" is a building or portion of a building used primarily for detentionand correctional occupancies where some degree of restraint or security is required for a timeperiod of twenty-four or more hours. Such occupancies include, but are not restricted to: Penalinstitutions, reformatories, jails, detention centers, correctional centers, and residentialrestrained care."Labeled" is to bear the department's insignia."Listed" is a piece of equipment or apparatus that has been approved by a testingagency to the appropriate standard."Local enforcement agency" is an agency of city or county government with powerto enforce local regulations governing the installation of a conversion vendor unit or medicalunit."Medical unit" is a type of self-propelled unit used to provide medical examinations,treatments, and medical and dental services or procedures, not including emergencyresponse vehicles, and which: Is transportable; Is temporarily placed and used; Is built on a permanent chassis; Includes at least one system; Is for temporary use only."One-year design plan" is a design plan that expires one year after approval or whena new state building code has been adopted."System" is part of a conversion vendor unit or medical unit designed to serve aparticular function. Examples include plumbing, electrical, or mechanical ite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 6 of 36[Statutory Authority: Chapter 43.22 RCW. WSR 16-13-119, § 296-150V-0020, filed 6/21/16,effective 6/21/16; WSR 05-23-002, § 296-150V-0020, filed 11/3/05, effective 12/4/05.Statutory Authority: RCW 43.22.34043.22.340,, 43.22.40043.22.400,, 43.22.43243.22.432,, 43.22.43343.22.433,, 43.22.43443.22.434,, 43.22.48043.22.480,,and 43.22.48543.22.485,, 2002 c 268, and chapter 43.22 RCW. WSR 03-12-044, § 296-150V-0020, filed5/30/03, effective 6/30/03. Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296150V-0020, filed 8/31/99, effective 10/1/99.]296-150V-0030How is this chapter enforced?(1) To enforce this chapter, we or another governmental inspection agency will inspecteach conversion vendor unit or medical unit manufactured, sold, leased, or used inWashington state as required by this chapter.(2) We will inspect all alterations.(3) We will conduct inspections during normal work hours or at other reasonable times.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0030, filed 8/31/99,effective 10/1/99.]296-150V-0040Is manufacturing information kept confidential?We will only release manufacturing information such as design plans, specifications,and test results according to the requirements of the Public Records Act (see RCW 42.17.310(1)(h)) unless we are ordered to do so by a court or otherwise required by law.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0040, filed 8/31/99,effective 10/1/99.]296-150V-0050Can you prohibit the sale or lease of a conversion vendor unit or medicalunit?(1) We may prohibit the sale or lease of your conversion vendor unit or medical unitbecause it is unlawful for any person to sell, lease, or offer for sale a conversion vendor unit ormedical unit within this state if it violates any of the requirements of this chapter.(2) If an inspection reveals that a conversion vendor unit or medical unit violates thischapter, we may post a notice prohibiting the sale or lease of a conversion vendor unit ormedical unit.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0050, filed 8/31/99,effective cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 7 of 36296-150V-0060Who handles consumer complaints about conversion vendor units ormedical units?(1) Consumers may file complaints within one year of the date of manufacture.(2) The complaint should be in writing and describe the item(s) that may not complywith this chapter.(3) After we receive the complaint, we will send the manufacturer and the dealer acopy of the complaint.(4) The manufacturer and/or dealer have thirty days to respond. We will base ouractions on the response.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0060, filed 8/31/99,effective 10/1/99.]296-150V-0070Do you have reciprocal agreements with other states to inspectconversion vendor units and medical units?(1) We will enter into reciprocal agreements with states that have inspection standardsequal or greater than our standard.(2) When we have a reciprocal agreement with another state:(a) The reciprocal state inspects the conversion vendor units and medical unitsmanufactured in that state before shipment into Washington to ensure compliance with ourlaws. After inspection, the reciprocal state applies our insignia.(b) The department inspects conversion vendor units and medical units manufacturedin Washington before shipment into the reciprocal state to ensure compliance with their laws.After inspection, we apply the insignia of the reciprocal state.(3) We have reciprocal agreements on file.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0070, filed 8/31/99,effective 10/1/99.]296-150V-0080Do you allow a local enforcement agency to inspect conversion vendorunits and medical units at the manufacturing location?(1) A local enforcement agency (city or county), under contract with us, can inspectconversion vendor units and medical units. In some cases, another agency's contracts may belimited to specific portions of an inspection at specified manufacturing ?cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 8 of 36(2) After approving a unit, the local enforcement agency will attach the insignia whichindicates that the unit has passed inspection.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0080, filed 8/31/99,effective 10/1/99.]296-150V-0100What happens if I disagree with your decision regarding my compliancewith this chapter?(1) If we determine that you are in violation of this chapter, you will receive a notice ofnoncompliance.(2) If you disagree with our decision, you can send us a written request for a hearing,stating why you disagree.(3) After we receive your hearing request, we will:(a) Schedule a hearing within thirty days after we receive your request;(b) Notify you of the time, date, and place for the hearing. If you fail to appear, yourcase will be dismissed;(c) Hear your case;(d) Send written notice of our decision to you.(4) If you disagree with our decision, you may appeal it under the AdministrativeProcedure Act, chapter 34.05 RCW.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0100, filed 8/31/99,effective 10/1/99.]296-150V-0110Do you have an advisory board to address conversion vendor unit andmedical unit issues?The factory assembled structures (FAS) board advises us on issues relating toplumbing, mechanical, electrical, inspections, and rule adoption for conversion vendor unitsand medical units. (See RCW 43.22.42043.22.420.).)[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0110, filed 8/31/99,effective 10/1/99.]296-150V-0120Where can I obtain technical assistance regarding conversion vendor unitsor medical e 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 9 of 36We offer field technical service to conversion vendor unit and medical unitmanufacturers for an hourly fee. (See WAC 296-150V-3000296-150V-3000.).) Field technical service mayinclude evaluation, consultation, plan examination, interpretation, and clarification of technicaldata relating to the application of our rules. It does not include inspections.[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0120, filed 8/31/99,effective 10/1/99.]296-150V-0140Do you allow the use of alternate materials, design, or method ofconstruction?An applicant may apply for the use of alternate materials, design, or methods ofconstruction different from the requirements of this chapter by filing a written request with thedepartment.(1) Responsibilities of the applicant. The applicant must submit in writing thefollowing information:(a) Name, address, and phone number;(b) The specific requirement or requirements from which the alternate material, design,or method of construction is requested;(c) Justification that the requirements of this chapter cannot be met without usingalternate materials, design, or method of construction;(d) How the use of alternate materials, design, or method of construction will achievethe same result as the requirement and any specific alternative measures to be taken to showthe alternate provides the same level of protection to life, safety and health as therequirements;The department has a form that you may use for your request. Please contact us atthe address shown in WAC 296-150V-0020296-150V-0020,, Definitions.(2) Responsibilities of the department. The department will provide a writtenresponse to the applicant within thirty days of receipt of the written request. The writtenresponse will state the acceptance or denial of the request, including the reasons for thedepartment's decision. At a minimum the department will base its decision on:(a) The applicant's request as described in subsection (1) of this section;(b) Research into the request;(c) Expert advice.(3) Applicant's response to denials. The applicant may appeal the department'sdecision by following the procedure in WAC 296-150V-0100296-150V-0100.[Statutory Authority: RCW 43.22.34043.22.340,, 43.22.35043.22.350,, 43.22.35543.22.355,, 43.22.36043.22.360,, 43.22.40043.22.400,, 43.22.432,43.22.432,43.22.433,, 43.22.43443.22.43343.22.434,, 43.22.45043.22.450,, 43.22.48043.22.480,, and 43.22.48543.22.485. WSR 00-17-148, § 296-150V0140, filed 8/22/00, effective 9/30/00. Statutory Authority: Chapter 43.22 RCW. WSR 99-18069, § 296-150V-0140, filed 8/31/99, effective cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 10 of 36296-150V-0200Who must obtain conversion vendor unit or medical unit insignia?(1) You must obtain an insignia from us for each conversion vendor unit or medical unitmanufactured, sold, leased, or used in Washington state.(2) You do not need an insignia for a conversion vendor unit or medical unit if a unitwas manufactured prior to July 1, 1968. (See RCW 43.22.37043.22.370.).)(3) You must obtain an insignia when conversion vendor units or medical units arealtered in Washington state.(4) You must obtain an alteration insignia when a conversion vendor unit or medicalunit is damaged in transit after leaving the manufacturing location or during an on-siteinstallation and an alteration or repair is necessary. The insignia indicates the conversionvendor unit or medical unit was altered or repaired.(5) You must have an approved design plan and pass our inspection before we willattach an insignia.Note:All conversion vendor units and medical units must have insignia if they are altered; this includes the exceptions insubsection (2)(a) and (b) of this section.[Statutory Authority: Chapter 43.22 RCW. WSR 16-13-119, § 296-150V-0200, filed 6/21/16,effective 6/21/16; WSR 99-18-069, § 296-150V-0200, filed 8/31/99, effective 10/1/99.]296-150V-0210What are the insignia requirements?(1) If you are applying for insignia, you must have your design plan approved whenrequired by WAC 296-150V-0300 and your conversion vendor unit or medical unit inspectedand approved by us.(2) If you are a manufacturer, dealer, or owner applying for an alteration insignia, youralteration must be inspected and approved by us. Approval of the design plan may also berequired.(3) We will attach the insignia to your conversion vendor unit or medical unit after:(a) We receive from you the required forms and fees listed in WAC 296-150V-3000296-150V-3000;;and(b) Your conversion vendor unit or medical unit has passed final inspection.[Statutory Authority: Chapter 43.22 RCW. WSR 16-13-119, § 296-150V-0210, filed 6/21/16,effective 6/21/16; WSR 99-18-069, § 296-150V-0210, filed 8/31/99, effective 10/1/99.]296-150V-0220How do I obtain insignia information and the required forms?Upon request, we will provide you with a packet of information that includes therequired forms. Our address is noted in the definition of "department" in WAC /wac/default.aspx?cite 296-150V&full true2/22/2019
Chapter 296-150V WAC:Page 11 of 36[Statutory Authority: Chapter 43.22 RCW. WSR 99-18-069, § 296-150V-0220, filed 8/31/99,effective 10/1/99.]296-150V-0230What are the insignia application requirements?(1) If you are requesting insignia for conversion vendor units or medical units yourcompleted application must include:(a) A completed design plan approval request form when required by WAC 296-150V0300;;0300(b) When required by WAC 296-150V-0300296-150V-0300,, one complete set of design plans,specifications, engineering analysis and test procedures and results (when applicable), plusone additional set for each manufacturing location where the design plan will be used;(c) For medical units at least one set of design plans must have an original wet stampfrom a professional engineer or architect licensed in Washington state. For conversion vendorunits a professional engineer or architect stamp is only required on the structural load test orcalculations required by WAC 296-150V-09302
296-150V-0500 When is an inspection required? 296-150V-0510 How do I request an inspection? 296-150V-0520 What happens if my conversion vendor unit or medical unit passes inspectio